Heat exchanger UIK–PRWC-40

Heat exchanger UIK–PRWC-40

Heat exchanger UIK–PRWC-40 has been designed as a device used to exchange heat between two carriers, i.e. water of process parameters in the primary and secondary circuit of pipelines supplying air cooling system in underground workings (supplying cold water down the mine and returning warm water up). The purpose of heat exchange is cooling down the carrier in the secondary circuit. Circulation of working carriers together with pipelines compose communicating vessels systems. The design of the exchanger (number of modules, construction of module) results from the operating conditions and it is selected to given process parameters.
This allows its proper selection and achieving maximum, expected cooling parameters. Heat exchanger UIK–PRWC-40 can be applied in workings of "a", "b" or "c" level of methane explosion hazard zones and to class A and B of coal dust explosion hazard zones.

TECHNICAL SPECIFICATION

Heating power of a single segment 765 / 950 [kW]
Segment length 4 / 5 [m]
Kerb weight of segment 1115 / 1394 [kg]
Number of segments in the system 4/6/8 [pcs]
Rated diameter of segments DN300
Rated diameter of connectors DN200 (150)
Hazard category according to 97/23/EC (PED) I
Group fluid 2
Connection flanges acc. to PN-EN 1092-1
Type of medium in circuits process water
Max. pressures in the circuits: primary
40[bar]
secondary
40[bar]
Flow rate in the circuits:
primary
secondary
primary
300[m3/h]
secondary
280[bar]
Operating temperature 0 ÷ 60[ºC]
Filtering accuracy 800[μm]